Trade Tools

Max Demand & Diversity

Diversity, maximum demand, supply.

in testingelectriciansiteandroid

Add the loads and circuits in a house and get the maximum demand after On-Site Guide diversity, in amps and kVA, against a 60, 80 or 100 A supply fuse. Handy for EV chargers, showers and rewires.

How it works, a worked example and screenshots ↓

Pay once, no subscription, no ads.

Platform
Android
Version
1.0
Source
Private source · Studio product
Price
£3.99

Runs on your phone, no internet needed. When it is on Google Play, updates will come through Play next time you're online.

Want to know when it launches? Email forestforge.dev@gmail.com.

Max Demand & Diversity artwork
Max Demand & Diversity app screen
Screenshot from the Android app

What it does

Max Demand & Diversity adds up the loads and circuits in a house, applies the On-Site Guide diversity allowances, and gives the maximum demand in amps and kVA to compare with the supply fuse. It is the quick check before adding an EV charger, a shower or a heat pump.

Who it's for

Electricians quoting rewires, EV charge points, showers and extensions, and anyone asking the DNO for a bigger supply.

How to use it

  1. 1Choose the supply fuse: 60, 80 or 100 A.
  2. 2Add each load or circuit with its type and current or rating (or enter kW).
  3. 3Say whether the cooker unit has a socket.
  4. 4Read the maximum demand after diversity and the headroom against the fuse.

Inputs and outputs

You enter

  • Supply (cut-out) fuse rating
  • Each load: name, type, current or circuit rating (or kW at 230 V)
  • Socket in the cooker control unit, yes or no

You get

  • Maximum demand after diversity in amps and kVA
  • Connected load before diversity
  • Headroom (or shortfall) against the supply fuse
  • The diversified figure for each load type

Worked example

A house with an electric shower

Given

  • 100 A supply
  • Lighting 10 A; two 32 A rings; cooker 40 A
  • Electric shower 9.5 kW (41.3 A); immersion 3 kW (13 A)

Working

  1. Lighting: 66 % of 10 A = 6.6 A
  2. Cooker: 10 A + 30 % of 30 A = 19.0 A
  3. Shower: 100 % = 41.3 A; immersion: no diversity = 13.0 A
  4. Sockets: 100 % of 32 A + 40 % of 32 A = 44.8 A

Result

124.7 A (28.7 kVA) after diversity: over the 100 A fuse by 24.7 A, so talk to the DNO before adding more.

An example only: your job will differ, so check the figures against the working in the app.

Features

  • House maximum demand after On-Site Guide diversity
  • Loads entered in amps or kW
  • Headroom against a 60, 80 or 100 A supply fuse
  • Handy for EV chargers, showers, heat pumps and rewires
  • Formulas and working shown, with a clear guide-only note
  • Copy, print to PDF, export JSON or open the result in the Electrician Suite
  • Works offline, no account, no ads

Screenshots

The tool with its starting values
The tool with its starting values
Formulas, working and the results panel
Formulas, working and the results panel

Guide only

Household allowances from the IET On-Site Guide Appendix A. A guide only: check against the regulations, the DNO and the manufacturer's data. The app shows its formulas and working so you can check every figure. It is not a substitute for your own judgement, training or the published standards.