Maximum earth fault loop impedance for type B, C and D MCBs and RCBOs or any device from its disconnection current, the 80 % rule for cold readings, Ze + R1+R2, TT RCD limits and a pass or fail list for your measured circuits.

How it works, a worked example and screenshots ↓

Pay once, no subscription, no ads.

Platform
Android
Version
1.0
Source
Private source · Studio product
Price
£3.99

Runs on your phone, no internet needed. When it is on Google Play, updates will come through Play next time you're online.

Want to know when it launches? Email forestforge.dev@gmail.com.

Max Zs & Loop Check artwork
Max Zs & Loop Check app screen
Screenshot from the Android app

What it does

Max Zs & Loop Check gives the maximum earth fault loop impedance for type B, C and D MCBs and RCBOs, or any device from its disconnection current, applies the 80 % rule for readings taken cold, adds Ze and R1+R2, and gives a clear pass or fail for your measured circuits. A TT tab covers RCD limits.

Who it's for

Electricians testing new work, periodic inspectors filling in an EICR, and apprentices learning where the tabulated limits come from.

How to use it

  1. 1Pick the protective device type and rating.
  2. 2Enter Ze and the measured R1+R2, and choose whether to correct R1+R2 to 70 °C.
  3. 3Read the maximum Zs, the 80 % figure and your calculated Zs with pass or fail.
  4. 4Use the Check readings tab for a list of circuits, or TT / RCD for installations with an earth electrode.

Inputs and outputs

You enter

  • Protective device: type B, C or D MCB/RCBO, or another device with its Ia
  • Rating In (A)
  • Ze, the external loop impedance (Ω)
  • R1+R2 measured at room temperature (Ω)
  • Correction of R1+R2 to 70 °C, yes or no

You get

  • Maximum Zs for the device
  • 80 % limit for readings taken cold
  • Calculated Zs = Ze + R1+R2, with pass or fail
  • Prospective fault current at that Zs
  • The full table of maximum Zs for every rating

Worked example

A type B 32 A circuit

Given

  • Type B MCB, 32 A
  • Ze 0.35 Ω, R1+R2 0.50 Ω

Working

  1. Ia = 5 × 32 = 160 A (instantaneous trip)
  2. Max Zs = 230 V × 0.95 ÷ 160 A = 1.37 Ω
  3. 80 % rule = 0.8 × 1.37 = 1.09 Ω
  4. Zs = 0.35 + 0.50 = 0.95 Ω
  5. Fault current = 230 ÷ 0.95 = 242 A

Result

0.95 Ω is under the 1.09 Ω cold limit: PASS.

An example only: your job will differ, so check the figures against the working in the app.

Features

  • Max Zs for B, C and D devices, or any device from Ia
  • The 80 % rule for cold readings, with pass or fail
  • Ze + R1+R2 with optional correction to 70 °C
  • TT installations: RA × IΔn ≤ 50 V
  • Formulas and working shown, with a clear guide-only note
  • Copy, print to PDF, export JSON or open the result in the Electrician Suite
  • Works offline, no account, no ads

Screenshots

The tool with its starting values
The tool with its starting values
Formulas, working and the results panel
Formulas, working and the results panel

Guide only

Worked from Zs = Uo × Cmin ÷ Ia, the basis of BS 7671 Tables 41.2–41.4. A guide only: check against the regulations and the device maker's data. The app shows its formulas and working so you can check every figure. It is not a substitute for your own judgement, training or the published standards.